Fifteen minutes to empty the station

Emergency blowdown of a compressor station · narrated

Duration
1:53
Year
2026

The case

An emergency shutdown isolates a compressor station holding 13.7 t of gas at 69 barg and opens two blowdown valves, each behind a 52 mm orifice. The target, 6.9 barg in about 15 minutes, is met with little margin: 6.77 barg. The gas left inside only cools to 1 °C because 205 t of pipe steel feed it heat; the real cold is downstream of the orifice: −19 °C in the gas and −10 °C at the vent pipe wall.

Topics

  • Blowdown
  • Process safety
  • Narrated explainer

Basis. Generic synthetic case built for this piece. No client data. Not a design verification.